Monday, August 4, 2014
Selenium Discharge Permit
I recently have been involved in several projects that deal with the difficulties associated with meeting Selenium Discharge Permits. Selenium is expensive to remove and difficult to test for accurately at the ppb level seen on some permits. Protecting the environment from pollution is a noble cause. Requiring end users to reduce selenium to levels lower then the incoming water content is absurd. It is this type of requirement that forces manufacturing to choose between losing profit or relocating manufacturing overseas.
Sunday, December 16, 2012
Increasing Cycles of Concentration thru Side Stream Softening
Reducing Cooling Tower Water Treatment Cost
Make Up | 3.0 CoC | |||||
TDS | 800 | 2400 | ||||
pH | 8.0 | 8.8 | ||||
Calcium | 160 | 480 | ||||
Alkalinity | 140 | 420 | ||||
°C | 45 | |||||
LSI | 2.45 | |||||
Silica | 9 | 27 | ||||
Chloride | 90 | 270 | ||||
Predicted Value @ 88% Ca Hardness Removal | ||||||
Make Up | 5.0 CoC | |||||
TDS | 800 | 4000 | ||||
pH | 8.0 | 9.2 | ||||
Calcium | 19 | 95 | ||||
Alkalinity | 140 | 700 | ||||
°C | 45 | |||||
LSI | 2.34 | |||||
Silica | 9 | 45 | ||||
Chloride | 90 | 450 | ||||
Assumptions: 1,000 Ton tower @ 70% load, 16 hours/day, 5 days/week, 52 weeks/year | ||||||
Annual Blowdown Savings: 4,960,404 liters/1,310,400 gallons |
Wednesday, October 31, 2012
Water Analysis: Las Vegas, Nevada USA
Make Up 3.2 CoC
Conductivity 904 2892
pH 8.2 8.7
Ca Hardness 188 601
Alkalinity 140 448
Chloride 65 208
Total Hardness 376 1203
Silica 8 25
Predicted LSI 2.4
This make up water sample from Las Vegas, NV USA was sampled and analyzed for use in a cooling tower application. By using the Langelier Saturation Index (LSI) we can predict the scale forming tendency of the water. Modern water treatment chemistry can prevent scale in waters with a LSI of 2.3-2.5. In waters with a pH greater then 8.5 that contain silica and magnesium hardness a mineral scale problem could occur. Under the right conditions Magnesium Silicate will form. This scale is a barrier to heat transfer and is one of the most difficult scales to remove. Silica levels are typically not a concern below 150ppm and can be handled as high as 200ppm with proper chemistry.
We can see from the above calculation that this tower can be operated safely at 3.2 Cycles of Concentration (CoC). At 3.2 CoC the water will have an LSI of 2.4 with a silica level of 25ppm. Both levels are within the acceptable range of modern water treatment chemistry. It is important to note that at a LSI of 2.4 the water is extremely scale forming. If the proper amount of water treatment chemical is not maintained at ALL times the system will rapidly develop scale. Las Vegas routinely has extremely high heat loads. For this reason the cooling system will experience high load. The conditions exist to form enough mineral scale in 24 hours to result in high enough head pressure to shut a chiller down. Professional, correct, and consistant water treatment is absolutely necessary in this environment.
Why does this information matter? Higher CoC results in lower water and chemical consumption. Consider an average casino with 8,000 tons (RT) of cooling operating 24 hours a day, 365 days per year at full load. By increasing tower cycles from 1.0 to 3.2 cooling tower make up is reduced by 12,487,730 liters (3,298,909 gallons) per day! This significant savings can easily be realized with a sound water treatment program and routine monitoring.
Thursday, October 25, 2012
Water Analysis: Hongqiao, China
Make up 8.0 CoC
Conductivity 304 2432
pH 7.6 8.7
Ca Hardness 55.5 444
Alkalinity 73 584
Chloride 28 224
Total Hardness 111 888
Silica 5.5 44
Predicted LSI 2.4
This make up water sample from Hongqiao China was sampled and analyzed for use in a cooling tower application. By using the Langelier Saturation Index (LSI) we can predict the scale forming tendency of the water. Modern water treatment chemistry can prevent scale in waters with a LSI of 2.3-2.5. In waters with a pH greater than 8.5 that contain silica and magnesium hardness a mineral scale problem could occur. Under the right conditions Magnesium Silicate will form. This scale is a barrier to heat transfer and is one of the most difficult scales to remove. Silica levels are typically not a concern below 150ppm and can be handled as high as 200ppm with proper chemistry.
We can see from the above calculation that this tower can be operated safely at 8.0 Cycles of Concentration (CoC). At 8.0 CoC the water will have an LSI of 2.4 with a silica level of 44ppm. Both levels are within the acceptable range of modern water treatment chemistry. It is important to note that at a LSI of 2.4 the water is extremely scale forming. If the proper amount of water treatment chemical is not maintained at ALL times the system will rapidly develop scale. Many facilities in Asia do not utilize modern chemical feed and control equipment. Instead they manually dose chemical and control bleed valves. It is not possible to maintain tight enough control with manual methods to achieve the water savings possible at 8.0 CoC without eventually forming scale. For this reason an automated chemical feed and control system must be installed.
Why does this information matter? Higher CoC results in lower water and chemical consumption. Consider a 1,000 ton (RT) tower operating 24 hours a day, 365 days per year at full load. By increasing tower cycles from 1.0 to 8.0 cooling tower make up is reduced by 1,611,938 liters (425,829 gallons) per day! This significant savings can easily be realized with a sound water treatment program and routine monitoring.
Wednesday, October 24, 2012
Water Analysis: Bali, Indonesia
Make up 3.5 CoC
Conductivity 1033 3615
pH 7.9 8.8
Ca Hardness 102.5 358.7
Alkalinity 176 616
Chloride 173 605.5
Total Hardness 205 717.5
Silica 26 91
Predicted LSI 2.4
This make up water sample from Bali Indonesia was sampled and analyzed for use in a cooling tower application. By using the Langelier Saturation Index (LSI) we can predict the scale forming tendency of the water. Modern water treatment chemistry can prevent scale in waters with a LSI of 2.3-2.5. In waters with a pH greater than 8.5 that contain silica and magnesium hardness a mineral scale problem could occur. Under the right conditions Magnesium Silicate will form. This scale is a barrier to heat transfer and is one of the most difficult scales to remove. Silica levels are typically not a concern below 150ppm and can be handled as high as 200ppm with proper chemistry.
We can see from the above calculation that this tower can be operated safely at 3.5 Cycles of Concentration (CoC). At 3.5 CoC the water will have an LSI of 2.4 with a silica level of 91ppm. Both levels are within the acceptable range of modern water treatment chemistry. It is important to note that at a LSI of 2.4 the water is extremely scale forming. If the proper amount of water treatment chemical is not maintained at ALL times the system will rapidly develop scale. Many facilities in Indonesia do not utilize modern chemical feed and control equipment. Instead they manually dose chemical and control bleed valves. It is not possible to maintain tight enough control with manual methods to achieve the water savings possible at 3.5 CoC without eventually forming scale. For this reason an automated chemical feed and control system must be installed.
Why does this information matter? Higher CoC results in lower water and chemical consumption. Consider a 1,000 ton (RT) tower operating 24 hours a day, 365 days per year at full load. By increasing tower cycles from 1.0 to 3.5 cooling tower make up is reduced by 573,008,400 liters (151,372,800 gallons) per year! This significant savings can easily be realized with a sound water treatment program and routine monitoring.
Conductivity 1033 3615
pH 7.9 8.8
Ca Hardness 102.5 358.7
Alkalinity 176 616
Chloride 173 605.5
Total Hardness 205 717.5
Silica 26 91
Predicted LSI 2.4
This make up water sample from Bali Indonesia was sampled and analyzed for use in a cooling tower application. By using the Langelier Saturation Index (LSI) we can predict the scale forming tendency of the water. Modern water treatment chemistry can prevent scale in waters with a LSI of 2.3-2.5. In waters with a pH greater than 8.5 that contain silica and magnesium hardness a mineral scale problem could occur. Under the right conditions Magnesium Silicate will form. This scale is a barrier to heat transfer and is one of the most difficult scales to remove. Silica levels are typically not a concern below 150ppm and can be handled as high as 200ppm with proper chemistry.
We can see from the above calculation that this tower can be operated safely at 3.5 Cycles of Concentration (CoC). At 3.5 CoC the water will have an LSI of 2.4 with a silica level of 91ppm. Both levels are within the acceptable range of modern water treatment chemistry. It is important to note that at a LSI of 2.4 the water is extremely scale forming. If the proper amount of water treatment chemical is not maintained at ALL times the system will rapidly develop scale. Many facilities in Indonesia do not utilize modern chemical feed and control equipment. Instead they manually dose chemical and control bleed valves. It is not possible to maintain tight enough control with manual methods to achieve the water savings possible at 3.5 CoC without eventually forming scale. For this reason an automated chemical feed and control system must be installed.
Why does this information matter? Higher CoC results in lower water and chemical consumption. Consider a 1,000 ton (RT) tower operating 24 hours a day, 365 days per year at full load. By increasing tower cycles from 1.0 to 3.5 cooling tower make up is reduced by 573,008,400 liters (151,372,800 gallons) per year! This significant savings can easily be realized with a sound water treatment program and routine monitoring.
Water Analysis: Chennai, India
Make up 3.0 CoC
Conductivity 1192 3576
pH 7.4 8.6
Ca Hardness 138.5 415.5
Alkalinity 182 546
Chloride 178 534
Total Hardness 277 1108
Silica 28.9 86.7
Predicted LSI 2.3
This make up water sample from Chennai India was sampled and analyzed for use in a cooling tower application. By using the Langelier Saturation Index (LSI) we can predict the scale forming tendency of the water. Modern water treatment chemistry can prevent scale in waters with a LSI of 2.3-2.5. In waters with a pH greater than 8.5 that contain silica and magnesium hardness a mineral scale problem could occur. Under the right conditions Magnesium Silicate will form. This scale is a barrier to heat transfer and is one of the most difficult scales to remove. Silica levels are typically not a concern below 150ppm and can be handled as high as 200ppm with proper chemistry.
We can see from the above calculation that this tower can be operated safely at 3.0 Cycles of Concentration (CoC). At 3.0 CoC the water will have an LSI of 2.3 with a silica level of 86ppm. Both levels are within the acceptable range of modern water treatment chemistry. It is important to note that at a LSI of 2.3 the water is extremely scale forming. If the proper amount of water treatment chemical is not maintained at ALL times the system will rapidly develop scale. Many facilities in India do not utilize modern chemical feed and control equipment. Instead they manually dose chemical and control bleed valves. It is not possible to maintain tight enough control with manual methods to achieve the water savings possible at 3.0 CoC without eventually forming scale. For this reason an automated chemical feed and control system must be installed.
Why does this information matter? Higher CoC results in lower water and chemical consumption. Consider a 1,000 ton (RT) tower operating 24 hours a day, 365 days per year at full load. By increasing tower cycles from 1.0 to 3.0 cooling tower make up is reduced by 567,039,500 liters (149,796,000 gallons) per year! This significant savings can easily be realized with a sound water treatment program and routine monitoring.
Wednesday, April 18, 2012
Corrosion Cell
Corrosion is a never ending battle in the water treatment industry. It is an electrochemical process in which a difference in electrical potential develops between two metals or between differeing parts of a single metal. Electrons flow from the anode to the cathode. Metal ions go into solution at the anode causing metal loss (corrosion). The speed at which the ions go into solution can be increased with higher conductivity waters (sea water, cooling water, boiler water). There are many types of corrosion and many more ways to control it. Having a basic understanding of the process will enable you to better choose a treatment option best suited for the application.
Subscribe to:
Posts (Atom)